P/N : AFBVA001/2/3-P001C00CC
Engineered for maximum safety, the FT10 liquid-cooled ball valve integrates a 4-tier safety-interlock system (end-face & handle buttons, fixed lock, and ball-lock linkage).
The valve employs multi-conditions verification and mechanical interlocking to ensure activation exclusively upon proper mating and operation. Once opened, it engages a positive lock to eliminate the risk of accidental disconnection or fluid loss, ensuring fail-safe operation.
Application
・ CDU(Coolant Distribution Unit)
・ Server
Feature
・ Single-pin interlocking design
・ High flow, low pressure drop
・ Reliable anti-aging performance
・ Foolproof

| Product General Characteristic | |
|---|---|
| Material | Stainless Steel / EPDM |
| Pressure Drop (Cv) | 30 |
| Fluid Loss(ml) | <5ml |
| Physical Characteristic | |
|---|---|
| Operating Pressure (psi) | 150psi |
| Min Burst Pressure (psi) | 300psi |
| Durability | 5000 Cycles |
| Environment Characteristic | |
|---|---|
| Operational Temperature | 10℃~65℃ |
| Non-Operational Temperature | -40℃~125℃ |
| Others | |
|---|---|
| Fluid | Water-glycol, pure water |